Ask us the plate details
We can read you the engine and emissions data off the specific unit before you commit, so your engineer or permit consultant has real numbers to work with.
EPA emissions tiers
The emissions tier is the one specification that can make a perfectly good generator the wrong generator. Here is what the tiers are, when the tier matters, and when it does not.
Ask about a specific unitThe short version
EPA tiers are progressively stricter limits on what a diesel engine may emit, mainly nitrogen oxides and particulate matter. They were phased in over roughly two decades, with Tier 1 arriving in the late 1990s and Tier 4 Final rolling out by size category through the early 2010s. Each step tightened the numbers; the last step tightened them enough that engines generally need exhaust aftertreatment to comply.
For a buyer, the practical rule is this. If the generator is genuine emergency standby, it sits under less stringent requirements, and a used Tier 2 or Tier 3 unit is often the better value. If the generator will supply power as a normal course of business, EPA's stationary engine standards push you toward Tier 4 certification, and a cheap older unit can turn out to be unpermittable for that use.
This is general information rather than a compliance determination. Confirm your requirement with the Florida Department of Environmental Protection, your county air program if it has one, and your local building and fire officials before you buy.
We can read you the engine and emissions data off the specific unit before you commit, so your engineer or permit consultant has real numbers to work with.
Get the load right before you filter on tier. How sizing works →
Standby, prime, and continuous ratings differ on the same machine. Sizes by kW →
Tier by tier
The first federal nonroad diesel standards, phased in during the late 1990s. Engines of this vintage are now old enough that condition, not emissions, is usually the deciding factor.
Phased in during the early 2000s. Mechanically straightforward, no aftertreatment, and a large share of the used industrial standby market in Florida sits here. Frequently the value choice for emergency use.
A further tightening in the mid to late 2000s, achieved mostly through engine design and fuel injection rather than exhaust treatment. Still simple to own, and newer than most Tier 2 stock.
The transitional step. Many engines in this band use partial aftertreatment, so what is fitted varies more between units than the label suggests. Check the specific machine.
The current standard for new nonroad and non-emergency stationary engines. Generally requires a diesel particulate filter, selective catalytic reduction with DEF, or both. Cleanest, most expensive, and the most to maintain.
A separate track. Under EPA's stationary engine rules, emergency engines are not required to meet Tier 4, which is why so much of the standby market remains Tier 2 and Tier 3 equipment.
Tier phase-in dates vary by engine power category, so two engines built the same year can fall under different requirements. The certification on the engine data plate is what counts, not the model year.
Emergency-only use, testing hours logged, no aftertreatment to service. Tier 2 or Tier 3 used equipment is usually the best value per kW.
Running as the main supply changes both the rating you need and the tier you can permit. Tell us this on the first call, because it changes everything downstream.
Mobile and towable units follow the nonroad standards, and some contracts and public projects specify a minimum tier. Check the contract before you check the price.
Usually not, if the generator is genuine emergency standby. EPA's stationary engine rules require Tier 4 certification for non-emergency stationary engines, while emergency stationary engines are held to less stringent standards. If instead the generator is your normal power source, or it runs regularly for anything other than testing and maintenance, the tier becomes a real constraint and you should confirm the requirement before buying.
Broadly, one that runs when normal power fails, plus limited hours per year for maintenance and testing. EPA allows emergency stationary engines up to 100 hours per year for maintenance and readiness testing, and up to 50 hours per year of that allowance for certain non-emergency use. Running a generator to save money on utility power is not emergency use, and treating it that way is how businesses end up out of compliance.
Yes, and for emergency standby it is often the sensible purchase. Used Tier 2 and Tier 3 units cost substantially less than Tier 4 Final equipment, have no aftertreatment to maintain, and are mechanically simpler. The limit is what you are permitted to do with them, not their availability.
Meeting Tier 4 Final generally requires exhaust aftertreatment: a diesel particulate filter, selective catalytic reduction with diesel exhaust fluid, or both. That adds purchase cost, adds DEF as a consumable, and adds a maintenance path that does not exist on an older engine. It also means the engine needs enough load to keep the aftertreatment working properly.
Tier 4 engines require ultra-low sulfur diesel, and SCR systems require diesel exhaust fluid, which has a shelf life and freezes at low temperatures, though that last point matters less in Florida than elsewhere. Older tier engines are more forgiving about fuel but less forgiving about smoke and noise near occupied buildings.
Air permitting in Florida runs through the Department of Environmental Protection's Division of Air Resource Management, and some counties administer their own programs. Installation, fuel storage, and life-safety requirements come from your local building department and fire official. We can tell you what tier a unit is certified to; what your specific site requires is a question for those authorities or your engineer.
Generator sales and delivery in Florida